Project Description
WESTSEA TITAN
REFRIGERATION SYSTEM REPAIR
Compressor No.1
– Release refrigeration gas out of systems |
||||||
– Overhaul exist freezer compressor by chemical liquid. | ||||||
– Fill up the oil | ||||||
– Renew oil separator by oxygen and acetylene | ||||||
– Install compressor into origin position | ||||||
– Renew suction valve, discharge valve by oxygen and acetylene | ||||||
– Testing all condenser controls of system No.1 (high, low pressure gauge, switch, and stop vale…) for working properly, replace new if required |
Compressor No.2: | ||||||
– Take out damaged compressor and install new compressor | ||||||
– Renew oil separator by oxygen and acetylene | ||||||
– Renew suction valve, discharge valve by oxygen and acetylene | ||||||
– Testing all condenser controls of system No.1 (high, low pressure gauge, switch, and stop vale…) for working properly, replace new if required |
Whole system – Renew two expansion valves by welding. – Connect all electric cable and piping – Cleaning system by nitrogen |
||||||
Pressure test and vacuum systems: | ||||||
– Pressure test system by nitrogen with pressure 22 kg/cm2. | ||||||
– Use liquid soap for check leak. | ||||||
– Confirm system no leak. | ||||||
– Vacuum systems down to pressure 76mmHg (vacuum pressure) and keep it 6 hours for test leak. | ||||||
– Top up R404A into system |